Analytical PI Tuning for Second-Order Plants with Monotonic Response and Minimum Settling Time
Abstract
This study presents two analytical closed-form PI controller tuning solutions for second-order plants with real poles, each achieving monotonic step response and minimum settling time. The first solution employs pole-zero cancellation, placing the controller zero at the slower plant pole and reducing the closed-loop dynamics to a critically damped second-order system. The second solution, applicable when the plant pole ratio is less than two, places all three closed-loop poles at a common location without cancelling any plant pole, yielding a closed-loop transfer function with a triple real pole and a zero. Despite retaining a closed-loop zero, this solution achieves strictly faster settling time than the pole-zero cancellation method in its region of applicability. The two solutions coincide at the boundary pole ratio of two and together form a continuous piecewise-analytical tuning covering the full range of plant pole ratios. This study further establishes that closed-loop transfer functions of the form a^n/(s + a)^n possess a maximum sensitivity Ms that is independent of the pole location a and depends solely on the order n, yielding universal robustness constants for each n. Numerical verification confirms the analytical results across multiple plant configurations.
Read the original paper
This page indexes public paper metadata. The manuscript remains with its original publisher and authors.